Sepem Noise Logger 352/155

Acoustic Leak Noise Loggers

  • Permanent or patrol leak monitoring of water networks
  • Deploys magnetically at fittings and valves
  • Up to 5-year battery life on a lithium cell
  • IP68 body, submersible to 1 m
  • Bi-directional radio data readout
  • Reads out with the SePem 01 Master

SePem noise loggers monitor water distribution networks for leaks automatically. Deployed magnetically onto fittings, valves and hydrants in valve chambers, each logger listens during the quiet night hours and records the leak-noise level — flagging new leaks long before they surface. Loggers can be left permanently for zone monitoring or moved on patrol, and results are read out by radio with the SePem 01 Master.

Compact and rugged in stainless steel and polypropylene, the SePem 155 is rated IP68 and submersible to 1 m, with bi-directional radio data and an adjustable sampling interval from 1 second to 1 hour. A single lithium cell delivers up to five years of service at standard settings.

Key Features

Automatic leak monitoring Listens during quiet night hours and records leak-noise levels.
Magnetic deployment Attaches magnetically to fittings, valves and hydrants - no tools.
5-year battery Lithium cell gives up to five years at standard settings.
IP68 submersible Stainless steel / polypropylene body submersible to 1 m.
Bi-directional radio 461-470 MHz data link, read out with the SePem 01 Master.
Flexible sampling Adjustable sample interval from 1 second to 1 hour.
Permanent or patrol Leave in place for zone monitoring or move on drive-by patrol.

Specifications

Device (SePem 155)

Dimensions (D x H)54 x 114 mm (without magnet and aerial)
Weight775 g (1.71 lb)
MaterialStainless steel, polypropylene
Memory64 kB
Processor16-bit microcontroller
OperationMagnetic activation via reed contact
Protection ratingIP68 (submersible to 1 m)

Measurement

Sampling rateAdjustable 1 s - 1 h

Data Transmission

Frequency461.0375 - 469.5625 MHz
CommunicationBi-directional radio data
Power20 mW

Power & Conditions

BatteryLithium metal cell
Operating timeUp to 5 years (standard settings)
Operating temperature-15 to 55 C
Humidity100 % r.h.

Assignment

Reads out withSePem 01 Master
CertificatesFCC

What's in the Box

  • SePem noise logger (155 or 352)
  • Magnet and aerial
  • Safety rope

Interested in the Sepem Noise Logger 352/155?

Request pricing, availability, or a hands-on demo from our team.